Description
Details
Description
The KSTAR UA100 Line Interactive UPS - 1000VA has been designed with an excellent charging mode. It not only offers great comprehensive power protection against surges and spikes but also provides pure voltage with an AC voltage stabilizer. It is easy to install and operate.
With a compact size and built-in self-diagnostic function, It makes an ideal backup power for terminal equipment, PC, station, and SOHO equipments.
Features
- AVR boost and buck
- Cold start function
- Smart RS-232/USB interface for power management
- Built-in self-diagnostic function
- Modem/LAN internet protection
- Generator compatible(Optional)
Specifications
Model | UA100 |
Capacity | 1000VA/600Watts |
Input | |
Normal Input Voltage | 10/120Vac or 220/230/240 Vac |
Operating Voltage Range | 81-145Vac/162-290 Vac |
Operating Frequency Range | 50/60 Hz (1+/- 10%) |
Output | |
Output Voltage Range (Batt. Mode) | Simulated Sinewave at nominal voltage +/-10% |
Frequency Range (Batt. Mode) | 50Hz or 60Hz +/- 1Hz |
Transfer Time | Typical 2-6ms, 10ms max |
Battery | |
Batter Type and Number | 12V/7Ah x2 |
Typical Recharge Time | 6-8 hours (To 90% capacity) |
Protection | |
Full Protection | Overload and Overcharge Protection |
Indicators | |
Indicator | AC Mode, Battery Mode, Load Level, Battery Level |
Alarm | |
Battery Mode | Sounding every 10 seconds |
Battery Low | Sounding every second |
Overload | Sounding every 0.5 seconds |
Battery Replacement | Sounding every 2 seconds |
Alarm Fault | Continuously Sounding |
Management | |
USB and RS-232 Port (Optional) | Supports Windows 2000/2003/XP/Vista/2008, Windows 7, Linux, Unix, and MAC |
Environment | |
Operating Temperature | 0-40 Degree Celsius |
Humidity Range | 0-95% (Non-condensing) |
Noise Level | |
Physical | |
Dimensions | 149.3mm x 338mm x 162mm (W x D x H) |
Net Weight | 7.8kg |
Standards | |
Safety | IEC/EN62040-1IEC/EN60950-1 |
EMC | IEC/EN62040-2IEC61000-4-2IEC61000-4-3IEC61000-4-4IEC61000-4-5IEC61000-4-6IEC61000-4-8 |